Current Transformers

Current Transformers

Current Transformer LZZW-20

Application: 20kV outdoor overhead power line
Structure: Outdoor, single phase, resin casting, and support type
Rated frequency: 50Hz, 60Hz
Rated insulation level: 24/65/125kV (IEC 24/50/125kV)
Rated secondary current: 5A,1A
Standard: GB/T 20840.1 & 2 (IEC 61869 -1 & 2)

Technical Data

Rated primary current (A)

Accuracy combination

Rated output (VA)

Protective accuracy limit factor (ALF)

Rated short-time thermal current Ith(kA/s)

Dynamic current Idyn(kA)

0.2 (0.2S)

0.5 (0.5S)

5P (10P)

5, 10, 15, 20, 25,
30, 40, 50, 75, 100,
150, 200

0.2 (S)/0.2 (S)
0.2 (S)/0.5 (S)
0.2 (S)/10P
0.5 (S)/10P
0.2 (S)/0.5 (S)/10P
0.2 (S)/10P/10P

10
15

15

15
20

10
15
20

100I1n

250I1n

250, 300

25

63

400, 500

31.5

80

600, 750

40

100

800, 1000, 1200

63

130

Remarks: Customizable secondary winding tapping and multi-ratio design.

★ Warning: Prohibit secondary open circuit.

Outline Drawing

CURRENT TRANSFORMER LZZW-20 (PO-408)-1.jpg

See how orders move from review to dispatch.

Reception, production, testing and shipment areas are organized to keep technical requirements, work progress and delivery records aligned.
Workplace & Customer Reception

Workplace & Customer Reception

Visitors and project teams have a clear place to review requirements, drawings and delivery details before work moves forward.
Organized Production Lines

Organized Production Lines

Defined work areas and orderly material flow help teams keep assemblies, components and order information aligned.
Testing & Verification

Testing & Verification

Routine checks and functional verification are completed against approved requirements before release.
Shipment & Delivery

Shipment & Delivery

Finished orders are checked, protected and organized for traceable handover and coordinated dispatch.

Built for recognised standards

Our documentation package supports project review with internationally recognised safety, quality and environmental marks.

Technical files for your review

Access the latest catalogue, technical parameters and certification files before you finalise your specification.
Go to Download Center

Product questions, answered

Clear guidance on selection, documentation, customization and project delivery.
Please provide the application, system rated voltage and frequency, continuous load current, short-circuit level, insulation level or BIL, and the required operating duty. Also include indoor or outdoor installation, altitude, ambient temperature, pollution level, control voltage, communication requirements, quantity, destination market and applicable standard. A single-line diagram, existing nameplate or project specification will make the review more accurate.
A recloser is generally used for automatic fault interruption and service restoration on distribution feeders. A circuit breaker provides repeated fault interruption, a load break switch is intended for rated-load switching within its specified capability, a disconnector provides an isolation point, and a fuse provides single-operation overcurrent protection. The final choice must be based on load current, fault level, protection coordination, switching frequency, installation method and operating philosophy.
Confirm the voltage class, frequency, rated current, short-circuit breaking and making duties, insulation level, creepage distance, mechanical or electrical endurance, enclosure protection, control supply and auxiliary contacts. The applicable IEC, IEEE, ANSI, GB or project-specific requirement should be stated in the inquiry. The approved data sheet and drawing, rather than only a general product family name, define the final supply.
Yes, a technical comparison can be made when sufficient information is available. Please send the existing model and nameplate, general arrangement and mounting dimensions, terminal interfaces, wiring diagram, interlocks, operating mechanism and electrical ratings. Similar voltage and current ratings do not by themselves confirm mechanical or electrical interchangeability, so approval is required before replacement.
Selection should consider the system grounding method, maximum continuous operating voltage, temporary overvoltage, required protective level, system insulation level, altitude, pollution severity and creepage distance. Mechanical loading, housing material and installation orientation also matter for outdoor equipment. Provide the system and site data so insulation coordination can be reviewed as a complete set.
Customization can be evaluated according to technical feasibility, validation requirements and order quantity. Typical requests include labels and packaging, terminal arrangements, mounting dimensions, control voltages, transformer ratios, accessories, communication functions and project documentation. Customized production should begin only after the technical specification and approved drawings are confirmed by both parties.
Product Enquiry

Define the right product configuration

Share the application and commercial information available at this stage. Our team will review the request against the product range and identify any details still required for quotation.

Application data

Rated voltage, installation environment and operating duty.

Technical scope

Applicable standard, configuration and required documents.

Delivery planning

Estimated quantity, destination and requested schedule.

Project details

Complete the fields below and include any specification points already confirmed.